Motor Differential Relay Testing (REM620) | How to Create Slope on Omicron Kit | Step-by-Step Guide
Автор: Barani Tech
Загружено: 2019-11-30
Просмотров: 8917
🔧 Master Motor Differential Protection Testing! In this video, we demonstrate step-by-step how to test a motor differential relay (ABB REM620) using the Omicron Test Kit, including how to create and verify the slope characteristic.
📌 What You’ll Learn:
✔ Basics of Motor Differential Protection (87M)
✔ Setting Up the Omicron Test Kit for REM620 Testing
✔ How to Create & Test Slope Characteristics (Slope 1 & Slope 2)
✔ Practical Tips for Accurate Differential Protection Testing
🔔 Subscribe for More Relay Testing Tutorials!
#DifferentialRelay #REM620 #OmicronTesting #MotorProtection #RelayTesting #ElectricalEngineering #powersystemprotection
Motor Differential Test by using Omicron Kit on Slop over REM620 relay
Here i have show how to test Motor differential test by using omicron kit
and also i use differential operating characteristic for testing.
From this video you can able to learn differential slop test method step by step very easy way
To find slop you can ref this video link for detail study.
• How to Perform SLOPE TEST on Differential ...
Motor details are
SN [KVA] = 22000
V[KV] = 6.6KV
P.f = 0.88
CT-Phase side = 300/1A
CT-Neutral side=300/1A
Relay setting are
ID low set = 10%
ID high set = 800%
Slope 1 = 20%
End section 1 =50 %
End section 2 = 150 %
Slope 2 = 100%
in this video you can able to see following test
Slope test.
a.shot test
b.search test
how to export report in omicron.
Доступные форматы для скачивания:
Скачать видео mp4
-
Информация по загрузке: