Refrigerated Air Dryer Shaking Violently - Troubleshooting and Repair
Автор: Compressed Air Friends
Загружено: 2025-11-21
Просмотров: 13
Customer called with a refrigerated air dryer that would shake violently every time they tried to start it up. After a short shutdown period, the unit became completely unusable due to severe vibration.
In this video, I walk you through the complete diagnostic process to identify the root cause of this problem. What appeared to be a mechanical issue turned out to be an electrical fault causing the compressor starter to chatter rapidly.
*The Problem:*
Unit shakes violently on startup
Multiple restart attempts - same result every time
Customer had to shut down for safety
*Diagnosis:*
Confirmed violent shaking condition
Traced issue to chattering compressor starter contactor
Found faulty phase monitor causing intermittent signal to starter coil
Phase monitor contacts causing starter to rapidly cycle on/off
*The Fix:*
Temporarily bypassed faulty phase monitor
Restored unit to full operation
Recommended permanent phase monitor replacement
*Equipment:*
QPNC-1250(E17) Refrigerated Air Dryer
460V 3-Phase
R410A Refrigerant
Located in Bay Minette, AL
This is a great example of how an electrical component failure can mimic mechanical issues. Always trace your circuits and don’t assume the obvious answer is the right one!
*⚠️ Important:* The temporary jumper bypasses protective features. Always replace faulty safety components as soon as possible.
-----
#HVAC #Troubleshooting #AirDryer #CompressedAir #IndustrialMaintenance #Electrician #HVACTech #Repair #Diagnostic
-----
If you found this helpful, please like, subscribe, and hit the notification bell for more troubleshooting and repair videos!