ESSENTIAL SWITCHGEAR NORMALIZE
Автор: BTG (BOILER TURBINE GENERATOR)
Загружено: 2023-12-24
Просмотров: 23
ENERGIZING ESSENTIAL LV SWITCHGEAR INCOMER-A and OPEN TIE BREAKER
❖ Go to 6.6 KV room essential board TIE breaker 30BMB00GS100
❖ Put trip selector switch to trip tie, Put sync CB selector CB IC-A and switch on sync function selector
❖ Go to Essential LV switchgear incomer-A and Ensure Sync on indication is ON
❖ Put Essential LV switchgear incomer-A in LOCAL mode press CLOSE switch, after this incomer-A CB will close and Tie breaker will OPEN
❖ Put Essential LV switchgear incomer-A CB in REMOTE mode and ensure in DCS remote indication is healthy